Commercial & Rooftop AC Repair in Los Angeles
Repair and maintenance of rooftop package units, condensing units and split systems for restaurants, salons, clinics, pharmacies, sports facilities and other businesses across Los Angeles.
$85 service call credited toward repair · 30-day labor / 90-day warranty on parts we supply
Updated November 2026
Quick facts
| Service call | $85 — credited toward the repair when you proceed |
|---|---|
| Warranty | 30-day labor · 90 days on parts we supply |
| Credentials | BEAR #A 50636 · EPA Section 608 Universal |
| Hours | Mon–Fri 09:00–19:00 Sat–Sun 10:00–16:00 |
Rooftop package units
Packaged AC and gas packs on the roof: blowers and belts, coils, drains, controls and refrigerant.
Condensing units and split systems
Condensers on roofs and in garages: capacitors, fan motors, compressors, TXVs and refrigerant leaks.
Frozen coils and water leaks
Iced evaporators, blocked condensate drains and overflowing pans traced to the cause.
Refrigerant leaks found and brazed
EPA Section 608 Universal certified. We find the leak, braze it, pressure test and pull a vacuum before recharging.
Blower motors and control boards
Burned blower motors, pulley and belt drives, and control boards tested before anyone condemns them.
NET terms & consolidated invoicing
One monthly invoice across all units and locations. NET 15 / NET 30 for qualified accounts.
Book online in Spanish
Online booking in both languages, for owners, managers and on-site staff.
How a commercial AC visit works
Tell us what the system is doing
Call or book online with what you're seeing: no cooling, weak air, water from the ceiling, ice on the unit, a fault code. Tell us where the unit sits, on the roof, in a garage or on a pad, and how we get to it.
Diagnosis on site
The $85 service call covers the diagnosis. We check airflow, filters, the condensate drain, capacitors and motors, the controls, and the refrigerant side with gauges when the symptoms point there.
Price before the work
You get the repair price before we start. If you go ahead, the $85 is credited toward the repair.
Repair, then prove it
After the repair we run the system and take readings: supply-air temperature, pressures, a vacuum that holds after leak work.
Paperwork for your records
An itemized report per unit: what failed, what we did, parts used, and warranty. 30 days on labor, 90 days on parts we supply.
What does commercial AC and HVAC repair cover?
Epic Star repairs commercial air conditioning and heating across Los Angeles: rooftop package units, gas packs, condensing units and split systems at restaurants, salons, clinics and other businesses. We diagnose on site for an $85 service call, credited toward the repair, and fix the existing system: blowers, drains, coils, leaks, compressors and controls.
How we repair commercial AC in Los Angeles
A dead AC at a business is a room full of customers and staff getting hot. We look for the reason a unit failed, not only the part that failed, so the next breakdown doesn’t follow a week later. Every example on this page is a job we did and wrote up.
Rooftop package units
A package unit keeps the whole system in one cabinet on the roof, with the ducts running down into the building. At a nail salon in Tarzana, the rooftop unit stopped moving air because its 1.5 HP belt-drive blower motor had burned out. The new motor’s shaft was a quarter inch smaller than the old pulley’s bore, so we fitted a correct pulley with the same drive ratio and a new belt. While the unit was open we cleaned the evaporator coil, put in new filters and brought a low charge up to spec, since a blower doesn’t strain for no reason.
At a sports facility in Studio City, a Lennox package unit froze solid with a punctured copper tube in the evaporator. Copper takes a braze, so we repaired the coil on the roof instead of replacing it, then proved it with a nitrogen pressure test and a vacuum that held at 270 microns. On a medical clinic’s packaged AC, the suction line was buried in ice down to the compressor; we let it thaw, added refrigerant and replaced the filter.
Heating on gas packs
Package units heat as well as cool. A pharmacy in Encino lost its heat when the rooftop gas pack flashed “high limit switch open.” All three switches tested closed and the wiring was good, so we pulled the control board and found ring cracks in its solder joints. We reflowed them on the roof instead of ordering a $300–400 board. The same kind of crack burned out a relay joint on a Turbo Air prep table at a Santa Monica restaurant.
Condensing units and split systems
Split systems put the condenser outside the space it cools, on a roof, a pad or in a garage. A restaurant in Downtown LA had three systems down at once, all with condensers near the ceiling of a hot underground garage: a drain-line problem, a failed capacitor and a refrigerant leak at a cracked copper bend, which we brazed. On a Culver City rooftop, an ICP Central condensing unit burned out its compressor. After the warranty compressor went in, the startup readings pointed to a stuck-closed TXV, and replacing it gave the new compressor the conditions it needs.
Water leaks and frozen coils
An AC makes water every hour it runs, and on a rooftop unit that water has a long way to fall. A physical therapy clinic in Mar Vista had water coming through the ceiling. The unit had no filter, the coil was packed with dirt and had frozen, and the drain trap was full of sludge. We cleaned the coil and the pan, rebuilt the drain with a proper slope and a cleanout tee, and fitted a filter.
What we found on these commercial jobs
Missing or clogged filters, blocked condensate drains, failed capacitors, burned blower motors, refrigerant leaks at punctured or cracked copper, a stuck TXV behind a dead compressor, and cracked solder on a control board. Several of these are cheaper to catch on a maintenance visit than to repair after a shutdown. For scheduled maintenance, see our AC tune-up.
Accounts and NET terms
Qualified businesses run on NET 15 or NET 30 terms with one consolidated monthly invoice across all units and locations, itemized per repair. For kitchen refrigeration, see commercial refrigerator and freezer repair, and for other business appliances, commercial appliance repair.
Credentials
California BEAR registered (#A 50636), EPA Section 608 Universal certified, $1,000,000 general liability insurance, 30-day labor warranty and 90 days on parts we supply. Online booking in English and Spanish.
Service area
We serve all of Los Angeles: the San Fernando Valley, Hollywood and Mid-City, the Westside, and the beach cities and South Bay.
Call (213) 205-2055
Tell us what the system is doing and where it sits, and ask about commercial accounts and NET terms.
Recent commercial AC jobs, with video
-
Downtown LA
Three HVAC systems down at one restaurant
- What the customer saw
- A restaurant in Downtown LA had all three of its HVAC systems out at once. The condensers hang near the ceiling of a hot underground garage with almost no ventilation.
- What we found
- Three separate faults: a full secondary drain pan from a drain-line problem, a failed capacitor that kept the condenser fan from starting reliably, and a refrigerant leak at a cracked copper bend.
- What we did
- We put the drain right, replaced the capacitor, found the leak by its oil residue and an electronic detector, brazed it and recharged. All three systems were running again.
-
Tarzana
Nail salon rooftop unit that stopped moving air
- What the customer saw
- A nail salon in Tarzana lost its AC. The rooftop package unit had stopped pushing air, and every quote the owner had collected was high.
- What we found
- The 1.5 HP belt-drive blower motor had burned out. The replacement motor had a 5/8-inch shaft, while the old pulley was bored for 7/8 inch.
- What we did
- We checked rotation on the bench, fitted a pulley with the correct bore and the same drive ratio plus a new belt, cleaned the evaporator coil, put in new filters and brought a slightly low charge up to spec.
-
Encino
Pharmacy gas pack with a cracked control board
- What the customer saw
- A pharmacy in Encino lost its heat. The packaged unit on the roof had shut its burners down and was flashing "high limit switch open."
- What we found
- All three limit switches tested closed and the wiring had continuity. On the back of the control board, the solder joints at the safety-circuit connector had ring cracks.
- What we did
- We reflowed the cracked joints right on the roof instead of ordering a $300–400 board. The board read the switches correctly, the burners lit and the pharmacy had heat again.
-
Mar Vista
Clinic ceiling leak from a rooftop unit with no filter
- What the customer saw
- Water was coming through the ceiling of a physical therapy clinic in Mar Vista, right where the AC ducts run.
- What we found
- The rooftop unit had no air filter. Its coil was choked with dirt and had frozen, and the drain trap was packed with black sludge, so the pan overflowed into the cabinet and the building.
- What we did
- We cleaned the coil with four rounds of foam, cleared the pan and drain, rebuilt the drain with a proper slope and a cleanout tee, refastened the insulation and fitted a correct filter. Supply air measured 60.6°F.
-
Studio City
Lennox package unit with a punctured evaporator tube
- What the customer saw
- The Lennox package unit on the roof of a sports facility in Studio City stopped cooling. The evaporator was frozen solid.
- What we found
- One copper tube in the evaporator had a puncture, possibly from someone chipping at the ice. A nitrogen search found that one leak and no other.
- What we did
- We brazed the copper coil on the unit instead of replacing it, the nitrogen pressure test held, the vacuum held at 270 microns, and we recharged the system, with the nameplate charge as the reference.
-
Culver City
Rooftop condensing unit with a burned-out compressor
- What the customer saw
- The AC at a building in Culver City had quit. The compressor in the ICP Central condensing unit on the roof had burned out completely.
- What we found
- After the warranty compressor went in, startup readings showed very high head pressure and very low suction. The TXV was stuck closed, and that restriction is what killed the old compressor.
- What we did
- We ran the full burnout procedure: refrigerant recovered, line set flushed, new compressor and filter-drier, pressure test, vacuum and recharge. Then we replaced the TXV.
-
Frozen packaged AC at a medical clinic
- What the customer saw
- The packaged air conditioner on a medical clinic's roof had frozen up.
- What we found
- The suction line in the compressor compartment was buried in thick ice all the way down to the compressor.
- What we did
- We let the ice melt, added refrigerant and replaced the air filter. The unit worked well after the service.
Photos from our commercial HVAC jobs












Issues we fix
-
Rooftop unit running but no air from the vents
Possible causes:
- Burned-out blower motor
- Broken or slipping blower belt
- Clogged filters or a matted evaporator coil
-
Water coming through the ceiling
Possible causes:
- Blocked condensate drain line or P-trap
- Frozen coil melting all at once
- Missing air filter letting dirt onto the coil
-
Ice on the coil or the suction line
Possible causes:
- Low refrigerant from a leak
- Dirty coil or clogged filter starving the airflow
- Weak blower
-
Condenser fan won't start or the unit keeps shutting off
Possible causes:
- Failed capacitor
- High head pressure tripping the pressure switch
- Condenser working in a hot, closed space
-
Burned-out compressor
Possible causes:
- Stuck-closed TXV restricting refrigerant flow
- Failing capacitor
-
Gas pack won't heat and shows a safety fault
Possible causes:
- Open high limit switch
- Cracked solder joints on the control board
- Wiring fault in the safety circuit
Frequently asked questions
What commercial AC and HVAC equipment do you repair?
Rooftop package units, including packaged AC and gas packs, condensing units and split systems at restaurants, salons, clinics, pharmacies, sports facilities and other businesses. Recent jobs include blower motors and belt drives, capacitors, frozen coils, blocked drains, refrigerant leaks, a compressor and TXV, and a control board.
How much does a commercial AC service call cost?
The service call is $85, and it's credited toward the repair if you go ahead. On commercial jobs we completed in Los Angeles, cleaning, drain work or a thaw and recharge on a business's rooftop unit typically runs $350–$570 across two jobs, a control-board repair at board level with no new part $220–$310, a rooftop blower motor or an on-roof coil braze $1,200–$2,300 across two jobs, and a restaurant job that covered three systems $2,550–$3,500. Those ranges include parts, labor and the $85 service call; you get the exact price in writing after diagnosis, before any work starts. Completed repairs carry a 30-day labor warranty and 90 days on parts we supply. Our cost guide at epicstarcor.com/blog/appliance-repair-cost-los-angeles/ lists more job types.
Do you repair refrigerant leaks on commercial units?
Yes. Section 608 certification is legally required for refrigerant work, and we hold EPA Section 608 Universal certification. We find the leak before recharging: by oil residue and an electronic detector at a Downtown LA restaurant, and with nitrogen on a Lennox package unit in Studio City, where we brazed the coil on the roof and pulled a vacuum to 270 microns.
Why does a rooftop unit leak water into the building?
One cause is condensate that can't get out. At a clinic in Mar Vista the unit had no filter, the coil was choked with dirt and froze, and the drain trap was packed with sludge, so the pan overflowed. A cracked drain pan can do the same with a clear drain. Switch the cooling off and call.
Do you replace whole commercial systems?
Our work on commercial HVAC is repair and maintenance of existing equipment. For a complete system replacement, we coordinate the project through licensed HVAC contractors, so you keep one point of contact from diagnosis through completion.
Do you offer NET terms and one invoice for several units?
Yes. Qualified businesses can set up NET 15 or NET 30 terms after a short approval, with one consolidated monthly invoice across all units and locations, itemized per repair. New accounts start per-visit.
What credentials and insurance do you carry?
Our technician is EPA Section 608 Universal certified for refrigerant handling. Epic Star Inc is California BEAR registered (#A 50636) and carries $1,000,000 in general liability insurance, with a certificate of insurance available on request.
Google reviews
★★★★★
Eric had a great and warmness about himself, efficient and knowledgeable awareness of the issues. Had accessed and completed the task in a minimal amount of time (12 minutes)
★★★★★
Refrigerator was checked thoroughly and repair ok ok
★★★★★
I’m very glad I had Ivan come to clean the extremely dirty hood over my stove. He came the same afternoon and did a very thorough job. After seeing how much work it was, I was very pleased with the price he charged me. I would definitely recommend this company.