Clogged mini-split condensate pump: a Daikin leaking water in Valley Village
The indoor unit sat level. Under the cover was a small drain pump that no water could reach because the pan outlet and the pump's filter were plugged.
Watch this repair on its own page
In this guide
Daikin mini-split leaking water: the first two checks
This wall-mounted Daikin ductless mini-split in Valley Village was leaking water into the room. The drain path to its condensate pump was clogged, and it took a few checks to find that.
Our first thought was that the unit wasn’t level. We checked it with a level, and it sat level.
Next we took the filters out and poured in a little water from a bottle. It ran out from the right corner, so we suspected a crack in the plastic drain pan.
Cover off: a dirty coil and a hidden drain pump
We took the plastic housing off. The pan had a lot of dust and dirt in it, and the coil was dirty too. Wash your filters more often. A mini-split cleaning visit washes the coil in place too.

There’s also a compact condensate pump in here, next to the coil. The blue box is the pump itself.

Next to it, the small clear box is the pump’s reservoir.

How does a mini-split condensate pump work?
Condensate, the water that drains off the coil, flows from the pan into the reservoir. A float rises with the water and signals the pump to turn on. It pumps the water out and goes back to standby.
What clogged the condensate pump?
We pulled the drain hose off the pan. The outlet was plugged solid with dust, slime and mold mixed together.

Inside the pump’s reservoir there’s a small mesh filter, and it was packed with dirt. The reservoir was dirty too.

Mold and dust had plugged the small rubber hose between the pan and the reservoir as well. No water could reach the pump, so the pump stopped pumping it out.

What we did
We washed the pump and its reservoir, then cleaned the drain pan with a chemical that kills mold. Last, we added a tablet to keep the drain line clean.
The test
With the parts back in, we put water into the drain pan to check the path condensate takes from the coil. It reached the reservoir and the pump kicked on. The pump emptied the reservoir and shut off. That’s a normal cycle.

The mini-split works again with the same pump. It didn’t need a new unit or a reinstall, only a cleaning from the drain pan to the pump.

The same leak on a Carrier in Hollywood Hills
A Carrier mini-split in Hollywood Hills was leaking the same way, and it has a condensate pump too. That pump’s filter is a sponge instead of a mesh, and it was clogged solid. The job has its own write-up: a clogged sponge filter in a Carrier mini-split’s condensate pump.
Two related jobs had other causes. On a Blueridge in Woodland Hills, mold packed the drain line and the unit leaked. A Daikin in Granada Hills smelled musty, and the mold was in its drain pan.
Mini-split cleaning and repair in Valley Village
Epic Star Appliance Repair and HVAC cleans and repairs mini-splits in Valley Village and across Los Angeles. See our mini-split repair service and the Valley Village service area. CA BEAR registered (#A 50636), EPA Section 608 Universal certified. Call or text (213) 205-2055.
FAQ
Why is my mini-split leaking water into the room?
On this Daikin mini-split the water wasn't getting to the condensate pump. Slime and mold had plugged the drain pan outlet and the hose to the pump, and the mesh filter in the pump's reservoir was packed with dirt. The water ran out of the indoor unit.
Does a mini-split have a condensate pump?
This Daikin has one: a compact pump under the plastic housing, next to the coil. The blue box is the pump and the small clear box is its reservoir. Some mini-splits have none. A Blueridge we worked on in Woodland Hills drained by gravity, with no pump.
How does a mini-split condensate pump work?
Condensate drains from the pan into the pump's reservoir. A float rises with the water and signals the pump to turn on. The pump empties the reservoir and goes back to standby.
My mini-split is level. Why is it still leaking water?
A level unit can still leak when the water can't reach the condensate pump. On this Daikin the indoor unit sat level, yet test water ran out the right corner because the pan outlet and the hose to the pump were plugged.
Does a clogged condensate pump need to be replaced?
This pump didn't need replacing. We washed the pump and its reservoir, cleaned the drain pan with a mold killer and added a drain tablet. After that the pump ran a normal cycle, and we didn't replace any parts.
What clogs a mini-split condensate pump?
Dust mixed with slime and mold plugged the drain pan outlet and the small rubber hose on this unit. The mesh filter in the pump's reservoir was packed with dirt, and so was the reservoir. The coil was dirty too, so wash the unit's filters more often. On a Carrier we cleaned in Hollywood Hills the filter is a sponge, and it was clogged solid.
Can I clean a mini-split condensate pump myself?
You can wash the unit's filters yourself, and we recommend doing it more often. Taking the pump and its reservoir apart is a job for a technician: the pump sits under the housing, next to the coil.
Do you clean and repair mini-splits in Valley Village?
Yes. Epic Star Appliance Repair and HVAC cleans and repairs mini-splits in Valley Village and across Los Angeles. Call or text (213) 205-2055, and tell us where the water shows up.
AC, heater or mini-split acting up? We cover LA and the Valley.
Call (213) 205-2055 or text a photo of the unit and its model sticker.