Daikin Mini-Split Repair and Cleaning in Los Angeles

Five Daikin mini-split jobs we documented across Los Angeles: a leak, error codes on two systems, a musty smell, and a two-zone system whose outdoor unit failed.

Call or text a photo of the issue. $85 service call, credited to your repair. Online booking in English and Spanish.

5.0 on Google · 38 reviews 30-day labor / 90-day warranty on parts we supply

Daikin mini-split mounted on the wall after the condensate pump was cleaned and put back in
Daikin mini-split in Valley Village that leaked water into the room; dust, slime and mold had kept the water from reaching its condensate pump.

Updated November 2026

Daikin mini-split jobs we have documented

Each section below is a Daikin job we worked on and wrote up, with a link to the full article. We are an independent repair company. Daikin systems fall under our mini-split repair and mini-split cleaning services.

Valley Village: leaking water, no water reaching the pump

A wall-mounted Daikin was leaking water into the room. The indoor unit sat level. With the filters out, test water ran out the right corner. Under the plastic housing we found a compact condensate pump next to the coil.

Dust, slime and mold had plugged the drain pan outlet and the small rubber hose to the pump’s reservoir. The mesh filter in the reservoir was packed with dirt, and so was the reservoir. No water could reach the pump, so it stopped pumping. We washed the pump and its reservoir, cleaned the drain pan with a mold-killing cleaner and added a tablet for the drain line. On the test the pump turned on, emptied the reservoir and went back to standby. No parts were replaced. The coil was dirty too, so washing the filters more often helps.

Full write-up with the video: a Daikin mini-split leaking water from a clogged condensate pump.

Hollywood: a new four-zone Daikin with UH and A5 codes

A new four-zone Daikin, installed by another crew, worked with all four rooms on. When the homeowner turned on one room, the system locked out. Three indoor units had logged UH and the fourth had logged A5, freeze protection.

The refrigerant lines were connected in the right order, but the control wires were crossed. Refrigerant went to a unit that was switched off, with no fan to move air, and its coil frosted over. We started Daikin’s connection check from the outdoor unit’s board. It ran each line in turn and re-mapped the crossed circuits in software. Then we tested each zone on its own.

Full write-up with the video: three units said UH, one said A5.

Tarzana: one head down with J9

One indoor head stopped working. Self-diagnostics from that unit’s remote returned J9, the outdoor gas pipe thermistor circuit. We unplugged the sensor harness and measured each thermistor at the connector. Most read about 28,000 ohms. The bottom one read 500. Daikin sells these thermistors as one harness, so the whole harness was replaced, and the head came back online.

Full write-up with the video: a Daikin J9 code and a thermistor harness.

Granada Hills: a musty smell and mold in the drain pan

A wall-mounted Daikin smelled musty, and the visit covered two indoor units. The black on the blower wheel was dried dust and dirt. The mold was down in the drain pan. We hung a cleaning bag under the unit, foamed the coil, then rinsed the coil and the blower wheel. The rinse water ran dark into the bucket, and the pan and wheel came out clean.

Full write-up with the video: a musty Daikin mini-split with mold in the drain pan.

San Fernando: a two-zone Daikin with a failed outdoor unit

Both rooms lost their AC because the shared outdoor unit had failed. A new Daikin system went in: an inverter outdoor unit on R-32 and two new indoor heads. Outside, the disconnect was replaced and each head was wired the same way, so the zones don’t get crossed. After brazing, the leak test and the vacuum, both heads were running.

Full write-up with the video: a two-zone Daikin mini-split swap, step by step.

Daikin mini-split service in Los Angeles

If your Daikin leaks, smells musty or shows a code, take a photo of the code before you reset anything. Call or text (213) 205-2055 and tell us what the unit is doing. CA BEAR registered (#A 50636), EPA Section 608 Universal certified, $1M general liability insurance.

Recent Daikin jobs

New Daikin inverter outdoor unit against a wall, with line-set covers running up the siding and a new disconnect box beside it
Two-zone Daikin mini-split whose outdoor unit had failed, leaving both rooms without AC: a new inverter outdoor unit on R-32 and two new indoor heads went in.📍 San FernandoRead the full case
Drain hose removed from a mini-split, with sludge blocking the drain pan outlet and water dripping into a basin
Same job: the drain hose pulled off the pan, with dust, slime and mold plugging the outlet.📍 Valley Village
Dirty foam dripping off the coil into the cleaning bag
Daikin mini-split cleaned in place in Granada Hills: dirty foam dripping off the coil into the cleaning bag📍 Granada Hills

Daikin issues we fix

  • Daikin mini-split leaking water into the room

    On the Valley Village job the indoor unit sat level, and test water ran out the right corner. Dust, slime and mold had plugged the drain pan outlet and the small hose to the condensate pump's reservoir, and the reservoir's mesh filter was packed with dirt. We washed the pump and its reservoir and cleaned the drain pan. No parts were replaced.

  • UH and A5 codes on a new multi-zone Daikin

    A new four-zone system in Hollywood worked with all four rooms on and locked out when one room ran alone. Three heads logged UH and one logged A5, freeze protection. The control wires were crossed, and Daikin's connection check re-mapped them in software without touching a wire.

  • One Daikin head down with a J9 code

    In Tarzana the remote's self-diagnostics returned J9, the outdoor gas pipe thermistor circuit. Measured at the connector, one thermistor read 500 ohms and most of the others read about 28,000. The thermistors come as one harness, and a new harness brought the head back.

  • Musty smell from a wall-mounted Daikin

    In Granada Hills the black on the blower wheel was dried dust and dirt. The mold was in the drain pan under the coil. We cleaned the coil, blower wheel and drain pan in place with foaming coil cleaner and a sprayer rinse.

  • Both rooms down on a two-zone Daikin

    Both heads of a two-zone system share one outdoor unit. In San Fernando that unit had failed, and a new Daikin system went in: an inverter outdoor unit on R-32 and two new indoor heads.

Frequently asked questions

  • Do you repair Daikin mini-splits?

    Yes. We diagnose, repair and clean Daikin ductless mini-splits across Los Angeles. The jobs on this page are ones we documented: a leak, error codes on two systems, a musty smell and a failed outdoor unit. Epic Star is an independent company, not a Daikin dealer.

  • Why is my Daikin mini-split leaking water into the room?

    On a Daikin in Valley Village the water wasn't reaching the condensate pump. Dust, slime and mold had plugged the drain pan outlet and the hose to the pump's reservoir, and the mesh filter in the reservoir was packed with dirt. We washed the pump and its reservoir and cleaned the drain pan, and the pump ran a normal cycle on the test.

  • What do Daikin UH and A5 codes mean?

    On a new four-zone Daikin in Hollywood, three indoor units logged UH and one logged A5, which is freeze protection. The exact definitions vary by model. The pattern pointed to the fault: the control wires were crossed, so refrigerant flowed through a unit that was switched off, and its coil iced up.

  • What does a J9 code mean on a Daikin mini-split?

    On the Tarzana job, J9 pointed to the outdoor gas pipe thermistor circuit. The code names the circuit, not the exact sensor, so we measured each thermistor at the connector. One read 500 ohms while most of the others read about 28,000, and a new thermistor harness brought the head back.

  • Why does my Daikin mini-split smell musty?

    On a Daikin in Granada Hills the mold was in the drain pan, where condensate collects under the coil. The black on the blower wheel was dried dust. Clean filters don't reach the pan, so we cleaned the coil, blower wheel and drain pan in place.

  • How much does Daikin mini-split cleaning cost?

    Mini-split cleaning runs $150–$450 per indoor unit, depending on its size and condition. Repairs start with the $85 service call, credited toward the repair, and you get a quote before work begins.

Verified source

Google reviews

Selected Google reviewsView at source

★★★★★

Eric had a great and warmness about himself, efficient and knowledgeable awareness of the issues. Had accessed and completed the task in a minimal amount of time (12 minutes)
Delma Braddy12 hours ago

★★★★★

Refrigerator was checked thoroughly and repair ok ok
Clara Cruz6 days ago

★★★★★

I’m very glad I had Ivan come to clean the extremely dirty hood over my stove. He came the same afternoon and did a very thorough job. After seeing how much work it was, I was very pleased with the price he charged me. I would definitely recommend this company.
Claire Hartunian2 weeks ago
Same-day service

Book a diagnostic/repair visit

Please enter your name.
Enter a valid 10-digit US phone number
Please enter a valid email.
Please enter your city or ZIP.
Use JPG, PNG, or WebP — max 3 × 5MB.
No spam, ever Background-checked techs

Talk to us about your Daikin repair

Or text a photo so we can bring the right part.